| Insulator type | D.C. anti-pollution type (Double-shed) | ||||
| GB standard No. | XZWP-160 | XZWP-210 | XZWP-240 | XZWP-300 | |
| Specified mechanical load (kN) | 160 | 210 | 240 | 300 | |
| Class | U160BLP | U210BSP | U240BSP | U300BP | |
| Nominal unit spacing (mm) | 170 | 170 | 170 | 195 | |
| Nominal diameter (mm) | 350 | 350 | 350 | 400 | |
| Nominal creepage distance (mm) | 545 | 545 | 545 | 635 | |
| Ball & socket size | 20 | 20/24 | 24 | 24 | |
| Electro mechanical failing load (kN) | 160 | 210 | 240 | 300 | |
| Mechanical routine test load (kN) | 80 | 105 | 120 | 150 | |
| D.C. withstand voltage(±) | Dry kV | 140 | 140 | 140 | 150 | 
| Wet (kV) | 55 | 55 | 55 | 60 | |
| Dry lightning impulse withstand voltage (kV) | 140 | 140 | 140 | 145 | |
| Power frequency puncture voltage(±) | Dry kV | 155 | 155 | 155 | 160 | 
| Wet (kV) | 60 | 60 | 60 | 65 | |
| puncture voltage inSF6(+) | 210 | 210 | 210 | 220 | |
| Weigh (kg) | 12.4 | 13.7 | 14.3 | 22.1 | |
| Applicable standard: GB IEC IS | |||||